AI Data Centers / The NX
The NX is Flexnode's repeatable building system for permanent AI data centers, configured around your site, power and compute requirements.
Defined system → engineering → facility
The NX is made from coordinated subassemblies developed around a defined architectural and engineering system. They come together as a permanent AI data center, with the facility configured to the site, power and compute requirements.
Core configurations
The NX scales from 4.5 to 18 MW of nominal critical IT capacity across four configurations.
| Specifications | NX-1 | NX-2 | NX-3 | NX-4 |
|---|---|---|---|---|
| Critical IT capacity | 4.5 MW | 9.0 MW | 13.5 MW | 18 MW |
| Facility load (peak) | 6.5 MW | 13.0 MW | 19.5 MW | 26.0 MW |
| Compute dimensions (W x L x H) | 28' x 100' x 18' | 50' x 100' x 18' | 75' x 100' x 18' | 100' x 100' x 18' |
| Rack capacity | 40-48 racks | 80-96 racks | 120-144 racks | 160-192 racks |
| Power density per rack | 230 kW standard; up to 600+ kW | |||
| Operational PUE | < 1.2 | |||
| Rack platform | Rack power | Cooling |
|---|---|---|
| NVIDIA GB200 NVL72 DGX | 132 kW | Direct liquid cooling |
| NVIDIA GB300 NVL72 DGX | 142 kW | Direct liquid cooling |
| NVIDIA GB300 NVL72 MGX | 142 kW | Direct liquid cooling |
| NVIDIA Vera Rubin VR200 NVL72 DGX | 230 kW | Direct liquid cooling |
| NVIDIA Vera Rubin VR200 NVL72 MGX | 230 kW | Direct liquid cooling |
Full site layout
The NX building connects to the power, cooling and support infrastructure each project requires. Select a group or an item to see where it sits.
The facility is planned around the selected NX configuration, the available power and the project's resilience requirements. Critical IT capacity is distinct from total facility demand.
The NX includes liquid-cooling interfaces for high-density compute. The rack and facility cooling loop and the outdoor heat rejection equipment are coordinated around the compute and the site.
Each facility's layout, exterior and site infrastructure respond to local conditions and project requirements.
Space, access and interfaces are planned for maintenance and future technology changes. Specific upgrades are evaluated against the facility and the equipment involved.